| AQUA-STOP®
MODEL CP-224 (Multi Zone Control Panel) |
||||
| Other specifications: Wiring distance for detectors: Up to 3000 feet. Wiring distance for valve control: Will vary between 400 and 600 feet and more. ( Depending the length of wire used the wire gauge has to be considered due to the voltage drop) Recommending wire gauge for detectors network: AWG #22 (Telephone cable). Detectors connection on each zone: In parallel. Capacity - detectors / zone: Up to 30 detectors. |
||||
| Water detectors: | ||||
| Model DFI (Flexible detectors): Plastic strips Self -adhesive, (2.5 inch length x 0.5 inch width x 0.010 inch thick) Two probes: Conductive silver ink circuitry. (width 0.100 inch) Wires crimped on the detector with two brass connectors.(included) Distance between two probes: 0.125 inch |
||||
![]() |
||||
| Flexible detector, model DF1 | ||||
| Model DS2 ( Solid detectors): Nylon solid block, secured by two screws or self-adhesive at the back. Dimensions: 2.5 inch Length x 0.5 inch Width x 0.5 inch Height. Two probes: Binder post aluminium. Wires secured on the detector by two aluminium screws. Distance between two probes: 0.750 inch. |
![]() |
|||
| Solid detector, model DS2 | ||||
Home R&D